OUTDOOR COMBINATION OIL-FIRED
FURNACE AND AIR CONDITIONING UNIT
MODEL OPA
INSTALLATION AND SERVICE MANUAL
Please read these instructions prior to installation, initial firing, and before
performing any service or maintenance.
These instructions must be retained by the homeowner for future reference by
qualified heating contractor.
Thermo Products, LLC
PO Box 217
MO-424 North Judson, IN 46366
ECN 4650-MA Phone: (574) 896-2133 Made In USA
: If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage, personal
injury, or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU FIND AN OIL LEAK:
Do not try to light any appliance.
Immediately call your oil supplier.
If you cannot reach your oil supplier, call the fire department.
Installation and service must be performed by a qualified installer, service
agency or the oil supplier. (These entities are referred to in these instructions
as a qualified heating contractor).
Vista de página 0
1 2 3 4 5 6 ... 90 91

Resumo do Conteúdo

Página 1 - MODEL OPA

OUTDOOR COMBINATION OIL-FIRED FURNACE AND AIR CONDITIONING UNIT MODEL OPA INSTALLATION AND SERVICE MANUAL Please read these inst

Página 2

All installations and services must be performed by qualified service personnel. 9 II. GENERAL INSTRUCTIONS The entire text of these instructions m

Página 3

All installations and services must be performed by qualified service personnel. 10 A. Codes and Clearances: The following items must be considered

Página 4

All installations and services must be performed by qualified service personnel. 11 5. Table 1 lists the required minimum clearances to combustible

Página 5

All installations and services must be performed by qualified service personnel. 12 surfaces. This clearance helps to promote air circulation under

Página 6

All installations and services must be performed by qualified service personnel. 13 condenser coil area are maintained. These openings are not to be

Página 7

All installations and services must be performed by qualified service personnel. 14 In addition, long term exposure of building materials to combusti

Página 8

All installations and services must be performed by qualified service personnel. 15 Figure 3: Installation of a Condensate Drainage Line on the Evapo

Página 9

All installations and services must be performed by qualified service personnel. 16 5. A readily accessible, design-certified, manual oil shutoff va

Página 10

All installations and services must be performed by qualified service personnel. 17 and tank. This requires insertion of the "by-pass" plug

Página 11

All installations and services must be performed by qualified service personnel. 18 Table 2: Burner Specifications and High and Low Fire Heating Perf

Página 12

All installations and services must be performed by qualified service personnel. 1 Contents SECTION PAGE I. SAFETY INFORMATION ...

Página 13

All installations and services must be performed by qualified service personnel. 19 H. Airflow Requirements and Sizing of Duct Work The duct system

Página 14

All installations and services must be performed by qualified service personnel. 20 6. The following method can be used to size ductwork when air

Página 15

All installations and services must be performed by qualified service personnel. 21 h. The resistance of the take-off and the outlet register (or re

Página 16

All installations and services must be performed by qualified service personnel. 22 Table 3: Suggested Duct Sizes for Homes, Quiet Offices, Or Simila

Página 17

All installations and services must be performed by qualified service personnel. 23 8. As a final step in the installation, the appliance must be ad

Página 18

All installations and services must be performed by qualified service personnel. 24 J. Electrical Wiring : This appliance must be grounded in accor

Página 19

All installations and services must be performed by qualified service personnel. 25 Typically, control wiring between the outdoor appliance and the i

Página 20

All installations and services must be performed by qualified service personnel. 26 3. All wiring sizes must comply with local codes or the National

Página 21

All installations and services must be performed by qualified service personnel. 27 Figure 4: The Fan Control Module NOTICE: It is important

Página 22

All installations and services must be performed by qualified service personnel. 28 2. Thermostat Anticipator Setting Proper control of the indoor

Página 23

All installations and services must be performed by qualified service personnel. 2 Contents SECTION PAGE VI. DEALER MAINTENANCE ...

Página 24

All installations and services must be performed by qualified service personnel. 29 Preferred method of adjustment: Using an analog ammeter on the l

Página 25

All installations and services must be performed by qualified service personnel. 30 Or in this case, _2.5 A. = 0.25 A.

Página 26

All installations and services must be performed by qualified service personnel. 31 Figure 7: Blower Motor Terminal Blocks & Wiring

Página 27

All installations and services must be performed by qualified service personnel. 32 IV. STARTUP PROCEDURES A. Heating System 1. Initial Startup:

Página 28

All installations and services must be performed by qualified service personnel. 33 Operating Instructions: i. STOP! Read the s

Página 29

All installations and services must be performed by qualified service personnel. 34 ii. If service is to be performed, turn off the electrical powe

Página 30

All installations and services must be performed by qualified service personnel. 35 f. Open the inspection cover on the upper mounting plate above t

Página 31

All installations and services must be performed by qualified service personnel. 36 NOTICE: To achieve proper combustion and the efficiencies listed

Página 32

All installations and services must be performed by qualified service personnel. 37 The supply air temperature should be measured in the supply air t

Página 33

All installations and services must be performed by qualified service personnel. 38 b. Turn on the fuel oil and cause the appliance to activate the

Página 34

All installations and services must be performed by qualified service personnel. 3 I. SAFETY INFORMATION This page and the following page contain r

Página 35

All installations and services must be performed by qualified service personnel. 39 After 15 to 20 minutes of continuous operation, the temperature r

Página 36

All installations and services must be performed by qualified service personnel. 40 c. Make certain the thermostat will automatically start and stop

Página 37

All installations and services must be performed by qualified service personnel. 41 B. Cooling Section 1. Initial Startup: : Refrigerant is under p

Página 38

All installations and services must be performed by qualified service personnel. 42 pressure-temperature chart on the unit for approximate system lin

Página 39

All installations and services must be performed by qualified service personnel. 43 Startup of a new cooling system and checkout of an existing syst

Página 40

All installations and services must be performed by qualified service personnel. 44 Refer to Example 3, in Appendix B: Calculations of this manual, f

Página 41

All installations and services must be performed by qualified service personnel. 45 Once the liquid line pressure is known, the refrigerant temperatu

Página 42

All installations and services must be performed by qualified service personnel. 46 V. INSTALLER'S INSTRUCTIONS TO USER After completing the i

Página 43

All installations and services must be performed by qualified service personnel. 47 VI. DEALER MAINTENANCE SAFETY DURING SERVICING AND INSPECTION :

Página 44

All installations and services must be performed by qualified service personnel. 48 excessive wear. Replace it, if required. Check and adjust oil pum

Página 45

All installations and services must be performed by qualified service personnel. 4

Página 46

All installations and services must be performed by qualified service personnel. 49 Figure 9, OPA Heat Exchanger Clean-out Ports and Related Componen

Página 47

All installations and services must be performed by qualified service personnel. 50 With access to the inside of the heat exchanger through the burne

Página 48

All installations and services must be performed by qualified service personnel. 51 3. Operational Check : Before troubleshooting, familiari

Página 49

All installations and services must be performed by qualified service personnel. 52 D. Supply/Return Air Blower Check in the blower compartment for

Página 50

All installations and services must be performed by qualified service personnel. 53 NOTICE: Remind the homeowner of the importance of monthly filter

Página 51

All installations and services must be performed by qualified service personnel. 54 6. Open the inspection cover on the upper mounting plate. 7.

Página 52

All installations and services must be performed by qualified service personnel. 55 VII. HOMEOWNER/USER INFORMATION AND ROUTINE MAINTENANCE : Never

Página 53

All installations and services must be performed by qualified service personnel. 56 4. Check to see if the high temperature limit switch reset but

Página 54

All installations and services must be performed by qualified service personnel. 57 The following maintenance points should be reviewed periodicall

Página 55

All installations and services must be performed by qualified service personnel. 58 ducts for any signs of collapse, holes, or excessive corrosion. R

Página 56

All installations and services must be performed by qualified service personnel. 5 The following warnings and cautions are found throughout the Therm

Página 57

All installations and services must be performed by qualified service personnel. 59 VIII. TROUBLESHOOTING : Power must be disconnected before serv

Página 58

All installations and services must be performed by qualified service personnel. 60 The operational condition of the flame sensor, or “cad cell”, ca

Página 59

All installations and services must be performed by qualified service personnel. 61 1. Is the disconnect switch or the circuit breaker serving the a

Página 60

All installations and services must be performed by qualified service personnel. 62 IX. REFERENCES 1. International Approval Services-U.S. Inc. a

Página 61

All installations and services must be performed by qualified service personnel. 63 X. APPENDIX A: SOURCES FOR REFERENCED STANDARDS 1. Air Condit

Página 62

All installations and services must be performed by qualified service personnel. 64 XI. APPENDIX B: CALCULATIONS Example 1: Problem: It is desir

Página 63

All installations and services must be performed by qualified service personnel. 65 Figure 15: Plan View of a Typical Residence Solution: If certai

Página 64

All installations and services must be performed by qualified service personnel. 66 This procedure can be repeated to determine the airflow for each

Página 65

All installations and services must be performed by qualified service personnel. 67 Therefore, choose a supply system static pressure drop of 0.2 in.

Página 66 - RmLiving

All installations and services must be performed by qualified service personnel. 68 However, there are two, 90 degree turns in the branch that will c

Página 67

All installations and services must be performed by qualified service personnel. 6 : Waterproof type connectors must be used when connecting electric

Página 68

All installations and services must be performed by qualified service personnel. 69 For section “C”, including a 7-inch, 90-degree elbow, the pressur

Página 69

All installations and services must be performed by qualified service personnel. 70 Next, the branch of the system, which includes segments “D” and “

Página 70

All installations and services must be performed by qualified service personnel. 71 (),.10.50.90614.0392*75.485*00123174.02058.082.1ininDD≅=⎥⎦⎤⎢⎣⎡+=

Página 71

All installations and services must be performed by qualified service personnel. 72 Example 3: Problem: Refrigerant measurements are made on the c

Página 72

All installations and services must be performed by qualified service personnel. 73 Now, the degree of superheat can be calculated. 48°F (Su

Página 73 - °F. What is the

All installations and services must be performed by qualified service personnel. 74

Página 74

All installations and services must be performed by qualified service personnel. 75 XII. APPENDIX C: ELECTRICAL SCHEMATIC AND CONNECTION DIAGRAM

Página 75

All installations and services must be performed by qualified service personnel. 76 XIII. APPENDIX D: SEQUENCE OF OPERATIONS A. SEQUENCE OF OPERAT

Página 76

All installations and services must be performed by qualified service personnel. 77 Control System ActionMain Burner OperationMode of OperationCall

Página 77 - Control System Action

All installations and services must be performed by qualified service personnel. 78 XIV. APPENDIX E: TROUBLESHOOTING FLOWCHARTS TURN THERMOSTAT TO

Página 78

All installations and services must be performed by qualified service personnel. 7 : For initial start-up of the appliance after installation, it ma

Página 79

All installations and services must be performed by qualified service personnel. 79 BLOWER RUNSNORMAL CYCLE?IS IGNITION ESTABLISHED?FURNACE OPERATES

Página 80

All installations and services must be performed by qualified service personnel. 80 PROPER COMBUSTION ACHIEVED?NoNoNoIS PUMP PRESSURE SETACCORDING TO

Página 81

All installations and services must be performed by qualified service personnel. 81 IS THE TEMPERATUREDIFFERENCE BETWEEN SUPPLYIS STACK TEMPERATURED

Página 82

All installations and services must be performed by qualified service personnel. 82

Página 83

All installations and services must be performed by qualified service personnel. 83 Notes for Air Conditioning Troubleshooting Guide 1.101.0 Check

Página 84

All installations and services must be performed by qualified service personnel. 84 2.101.0 Check to see if the condenser fan motor is excessively h

Página 85

All installations and services must be performed by qualified service personnel. 85 3.101.1 Dirty air filters may restrict the airflow across the

Página 86

All installations and services must be performed by qualified service personnel. 86 XV. APPENDIX F: SPECIFICATION SHEETSModel No.:OPA24-80 OPA30-80

Página 87

All installations and services must be performed by qualified service personnel. 87 APPENDIX G: REPLACEMENT PARTS LIST

Página 88

All installations and services must be performed by qualified service personnel. 88

Página 89

All installations and services must be performed by qualified service personnel. 8 : Carefully read and thoroughly understand the following guideline

Página 90

All installations and services must be performed by qualified service personnel. 89 XVI. APPENDIX H: OPA HEATING AND COOLING SYSTEMS TEST FORM Nam